Performance Characteristics:
Function diversity | Reliability &stability |
With PQ,VF,VSG,MPPT,DC voltage source and other operating modes. With one-time FM/voltage control,VSG,black start function. With off-grid switching function,support multi-machine parallel function. | Integrated industrial frequency isolation transformer,strong impact resistance,higher safety,suitable for off-grid micro-grid systems. |
Easy maintenance | Quick response |
Modular rack design,energy storage battery can be run independently,easy maintenance,good scalability. | Charge and discharge conversion time not exceeding 40ms and response time less than 30ms to meet scheduling needs or FM project applications. |
Efficient energy saving | Strong adaptability |
Three-level circuit design,high conversion efficiency, improved power utilization. | Excellent high and low voltage traversal,stable operation at SCR=1.05,strong grid adaptability. |
Product Parameters:
TYPE | Monet-100 | Monet-250 | Monet-500 | Monet-630 | Monet-250T | Monet-500T | |
DC Side Parameters | |||||||
Working voltage range | 550~900V | 550~900V | 550~900V | 600~900V | 500~900V | 500~900V | |
Full load voltage range | 550~900V | 550~900V | 550~900V | 600~900V | 500~900V | 500~900V | |
Max DC current | 100A*2 | 100A*5 | 100A*10 | 110A*10 | 110A*5 | 110A*10 | |
Input channel | 1/2 | 1/5 | 1/10 | 1/10 | 1/5 | 1/10 | |
Adaptable battery | lithium battery /lead-acid battery /photovoltaic module /flow battery | ||||||
Charging mode | BMS instruction/three-stage | ||||||
Working model | constant voltage/constant current/constant power/MPPT/AC voltage source/DC voltage source/VSG | ||||||
AC Side Parameters (connected) | |||||||
Max ac power | 110kVA | 275kVA | 550kVA | 693kVA | 275kVA | 550kVA | |
Rated AC power | 100kW | 250kW | 500kW | 630kW | 250kW | 500kW | |
Rated AC current | 144A | 361A | 722A | 909A | 361A | 722A | |
Rated AC voltage | 400Vac,3W+N+PE/3W+PE | ||||||
AC voltage range | 400Vac±15% | ||||||
Rated frequency | 50/60Hz,(±5Hz) | ||||||
THD | <3%(rated power) | ||||||
Power factor range | -1 lead ~+1 lag | ||||||
AC Side Parameters(disconnected) | |||||||
Rated AC voltage | 400Vac | ||||||
Voltage distortion | <3%(linear load) | ||||||
Rated frequency | 50/60Hz | ||||||
Overload capacity | 110 %for long-term operation,120 %for one minute | ||||||
Protection Function | |||||||
DC input protection | load switch +fuse | ||||||
AC input protection | circuit breaker +fuse | ||||||
Over-voltage protection | DC Type Il/AC Type ll | ||||||
Over-current protection | available | ||||||
Residual current detection | available | ||||||
Anti-islanding protection | available | ||||||
Common Params | |||||||
Max efficiency | 98.2% | 98.4% | 97.4% | 97.4% | |||
Dimension | 600*800*2000mm | 1200*800*2000mm | 1200*950*2100mm | 1400*950*2200mm | |||
Weight | 240kg | 350kg | 800kg | 800kg | 1200kg | 1650kg | |
Isolation mode | non-isolated | power frequency isolation | |||||
Protection class | IP21 | ||||||
Operating temperature | 25~60℃(derating above 45°C) | ||||||
Relative humidity | 0~95%(non-condensing) | ||||||
Cooling method | forced air cooling | ||||||
Noise | <70dB | ||||||
Altitude | 3000m(more than 3000m derating | ||||||
Communication interface | RS485/CAN 2.0/Ethernet | ||||||
Certification | EN 61000-6-1/EN 61000-6-2/EN 61000-6-3 IEC 61000,IEC 62477-1:2012,IEC 61727,IEC 62116,GB/T34120,GB/T34133 | ||||||
Note:The above models are typical configurations,and the number and type of modules can be flexibly adjusted according to the battery configuration and power demand. |