Availability: | |
---|---|
Quantity: | |
LD320()S2 | 0R7 | 1R5 | 2R2 | 4R0 | 5R5 | 7R5 |
KW | 0.75 | 1.5 | 2.2 | 5.5 | 7.5 | |
Frame size | A | B | C |
LD320()T4 | 0R7 | 1R5 | 2R2 | 4R0 | 5R5 | 7R5 | 11 | 15 | 18 | 22 | 30 | 37 |
KW | 0.75 | 1.5 | 2.2 | 4 | 5.5 | 7.5 | 11 | 15 | 18 | 22 | 30 | 37 |
Frame size | A | B | C | D |
LD320()T4 | 45 | 55 | 75 | 90 | 110 | 132 | 160 | 185 | 200 | 220 | 250 | 280 |
KW | 45 | 55 | 75 | 90 | 110 | 132 | 160 | 185 | 200 | 220 | 250 | 280 |
Frame size | E | F | G | H |
LD320()T4 | 315 | 355 | 400 | 450 | 500 | 560 | 630 | 710 | 800 |
KW | 315 | 355 | 400 | 450 | 500 | 560 | 630 | 710 | 800 |
Frame size | H | I | J | K | L |
220V | |||||||
Frame size | A | B | C | ||||
Model LD320- S2B | 0R7 | 1B5 | 2R2 | 4R0 | 5R5 | 7R5 | |
Applicable motor power KW | 0.75 | 1.5 | 2.2 | 4 | 5.5 | 7.5 | |
Applicable motor horsepower HP | 1 | 2 | 3 | 5 | 7.5 | 10 | |
Output | Rated output capacity KVA | 1.9 | 2.5 | 4.2 | 6.5 | 9.5 | 12.5 |
Rated output current A | 4 | 7 | 9.6 | 17 | 20 | 30 | |
Output frequency Hz | 0.01--400Hz | ||||||
Carrier frequeney range KHz | 1--16KHz | ||||||
Overload capacity | 150% of rated output current, can withstand 60S | ||||||
200% of rated output current, can withstand 3S | |||||||
Input 220V | Input current A | 7 | 9.4 | 16 | 23 | 24 | 31 |
Input voltage frequency | single phase 220V,50/60Hz | ||||||
Permissible voltage fluctuations | (-15%--+15%) | ||||||
Cooling system | Forced cold air | ||||||
Brake unit | built-in |
380V | ||||||||||||||||
Frame size | A | B | C | |||||||||||||
TYPE LD320- T4B | 0R7 | 1R5 | 2R2 | 4R0 | 5R5 | 7R5 | 11 | 15 | 18 | 22 | ||||||
Applicable motor power KW | 0.75 | 1.5 | 2.2 | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | ||||||
Applicable motor horsepower HP | 1 | 2 | 3 | 5 | 7.5 | 10 | 15 | 20 | 25 | 30 | ||||||
output | Rated output capacity KVA | 2.3 | 3.2 | 4.2 | 6.5 | 9.9 | 13.7 | 18.3 | 24.4 | 29 | 43 | |||||
Rated output current A | 2.1 | 3.8 | 5.1 | 9 | 13 | 17 | 25 | 32 | 37 | 45 | ||||||
Output frequency Hz | 0.01--400Hz | |||||||||||||||
Carrier frequency range KHz | 1--16KHz | |||||||||||||||
Overload capacity | 150% of rated output current, can withstand 60S | |||||||||||||||
200% of rated output current, can withstand 3S | ||||||||||||||||
input | Input current A | 3.4 | 5 | 5.8 10.5 | 14.6 | 20.5 | 26 | 35 | 38.5 | 46 | ||||||
Input voltage frequency | three-phase 380V.50/60Hz | |||||||||||||||
Permissible voltage fluctuations | (-15%--+15%) | |||||||||||||||
Cooling system | Forced cold air | |||||||||||||||
Brake unit | built-in | |||||||||||||||
380V | ||||||||||||||||
| Frame size | D | E | F | G | |||||||||||
TYPE LD320- T4B | 30 | 37 | 45 | 55 | 75 | 90 | 110 | 132 | 160 | 185 | 200 | |||||
Applicable motor power KW | 30 | 37 | 45 | 55 | 75 | 90 | 110 | 132 | 160 | 185 | 200 | |||||
Applicable motor horsepower HP | 40 | 50 | 60 | 75 | 100 | 125 | 150 | 175 | 215 | 250 | 270 | |||||
output | Rated output capacity KVA | 46 | 56 | 69 | 84 | 114 | 143 | 175 | 200 | 248 | 282 | 305 | ||||
Rated output current A | 60 | 75 | 91 | 112 | 150 | 176 | 210 | 253 | 304 | 345 | 377 | |||||
Output frequency Hz | 0.01--400Hz | |||||||||||||||
Carrier frequency range KHz | 1--16KHz | |||||||||||||||
Overload capacity | 150% of rated output current, can withstand 60S | |||||||||||||||
200% of rated output current, can withstand 3S | ||||||||||||||||
input | Input current A | 62 | 76 | 92 | 113 | 157 | 180 | 214 | 256 | 307 | 353 | 385 | ||||
Input yoltage frequency | three-phase 380V,50/60Hz | |||||||||||||||
Permissible voltage fluctuations | (-15%--+15%) | |||||||||||||||
Cooling system | Forced cold air |
380V | |||||||||||||
Frame size | H | I | J | K | L | ||||||||
TYPE LD320- T4B | 220 | 250 | 280 | 315 | 355 | 400 | 450 | 500 | 560 | 630 | 710 | 800 | |
Applicable motor power KW | 220 | 250 | 280 | 315 | 355 | 400 | 450 | 500 | 560 | 630 | 710 | 800 | |
Applicable motor horsepower HP | 300 | 340 | 380 | 430 | 485 | 400 | 545 | 615 | 667 | 747 | 947 | 1068 | |
output | Rated output capacity KVA | 338 | 385 | 431 | 485 | 546 | 615 | 692 | 769 | 862 | 969 | 1092 | 1231 |
Rated output current A | 426 | 465 | 520 | 585 | 650 | 725 | 820 | 860 | 950 | 1100 | 1280 | 1380 | |
Output frequency Hz | 0.01--400Hz | ||||||||||||
Carrier frequency range KHz | 1--16KHz | ||||||||||||
Overload capacity | 150% of rated output current, can withstand 60S | ||||||||||||
200% of rated output current, can withstand 3S | |||||||||||||
input | Input current A | 430 | 468 | 525 | 590 | 640 | 690 | 790 | 835 | 920 | 1050 | 11261460 | |
Input yoltage frequeng | three-phase 380V,50/60Hz | ||||||||||||
Permissible voltage fluctuations | (-15%--+15%) | ||||||||||||
Cooling system | Forced cold air |
characteristic parameter | |||
project | specifications | ||
IN-OUT | analog input | 2-way/voltage current signal switchable, voltage 0-10V, current 0-20mA | |
Digital input | 5 channels/optocoupler isolation, including 1 high speed pulse input, with a maximum input pulse frequency of up to 100KHz | ||
analog output | 2 channels/voltage output range 1-10V, current output range 0-20mA, output signal type can be switched | ||
Digital output | 2-way/optocoupler isolation/open collector output/rated current 20mA (DO, HDO) | ||
Digital pulse output | 2 channels/optocoupler isolation/open collector pulse (trequency or PWM) output (DO, HDO),including 1 channel of high-speed pulse output, the maximum output pulse frequency can reach 100KHz | ||
relay output | 2-way/Normally Open and Normally Closed Contact/250VAC-3A | ||
communication mode | Standard MODBUS-485 communication protocol | ||
control characteristic | control mode | V/F control; PG free vector control (SVC); With PG vector control | |
Frequency setting mode | Multiple setting methods such as keyboard setting, analog quantity setting, pulse setting, communication setting, etc | ||
Frequency control ange | 0.01-500.00Hz | ||
Frequency control accuracy | Digital setting: 0.01Hz; Analog setting: maximum frequency x 0.025% | ||
speed range | 1:200(SVC); 1:1000(FVC) | ||
Steady range | ±0.5%(SVC);±0.02%(FVC) | ||
Acceleration and deceleration time | 1.0-3600.0 seconds (acceleration and deceleration times can be set separately, and S characteristics can be switched) | ||
Inching control | Point frequency range: 0.00Hz-100.00Hz; Point acceleration time: 0.0s-3600s | ||
Starting torque | 0.5Hz 150%(SVC) adjustable, considering the capacity of the frequency converter; 3.0Hz 100%(V/F) | ||
Torque boost | Automatic torque increase; Adjustable manual torque increase of 0.1%-30.0% | ||
braking torque | Braking resistance braking (125%), DC braking (20%) | ||
DC braking | Braking time: 0.0s-36.0s; Braking current: 0.0%-100.0% | ||
timing control | Timing range: 0.0min-6500min | ||
Pid control | Built in PIO function for convenient closed-loop control of processes | ||
V over F curve | Linear, multi-point custom curve, 1.1-2.0 arbitrary descent curve | ||
Multi stage speed control | Buit-in simple PLC can control the maximum 16 speed frequency logic | ||
Carrier adjustable | Adjustable from 1.0 to 16.0kHz, adjustable according to module temperature | ||
Frequency setting signal | 10-+10,0-+10,4-20mA, high-frequency pulse, PWM pulse | ||
protection function | Overload capacity | G:150% 60s 200% 2s ; p:120% 60s 150% 1s | |
Instantaneous overcurrent/ short circuit protection | Automatically cut off output when the rated output current exceeds 200% | ||
Overvoltage/secondary voltage protection | When the DC voltage of the bus is too low (360V) or too high (800V), the motor stops freely (except during braking) | ||
Phase loss protection | When there is a phase loss at the input or output end, the motor stops freely | ||
Overheat protection | When the radiator temperature is ≥85 ℃, the motor stops freely; The temperature protection threshold can be freely set according to the ambient temperature | ||
motor protection | Analog input can be connected to temperature sensor inputs (PT100, PT000) to achieve motor overheating protection | ||
Stall protection | Using current sensors to detect stall prevention duning acceleration and daceleraion, and stall prevention during operation (action current can be set) | ||
ground protection | Using current sensors for detection | ||
Instant stop | By compensting for vatlage reducion though load feedback energy, the frequecy conveter can maintain continuous operation for a short petiod of time | ||
specifications stucture | Rated input | voltage:1/3PH 220V±20%;3PH 380V±20%;frequency:50Hz/60Hz±5% | |
Cooling and protection | ≤18.5kW:IP20>18.5kW:1IP10;Forced air cooling | ||
Usage environment | Temp:-10℃-+40℃ altitude: Not higher than 1000m; Indoor, without corrosive gases | ||
Save Environment | Temp:-20℃-+65℃ humidity:20-90%RH(No condensation)The vibration is less than 6m/S squared(0.6g) |
0.75/1.5/2.2KW High Performance Variable Frequency Drive for Fan/Pump/Mill/Lathe