Availability: | |
---|---|
Quantity: | |
Performance Characteristics:
Flexible and convenient | Efficient and intelligent |
Standard rack modular design, flexible configuration, convenient maintenance, convenient expansion. | The high efficiency version uses a single-stage DC/AC structure to improve system efficiency. |
DC/DC, DC/AC, STS different types of modules are freely matched, according to local conditions. | DC/DC and DC/AC are designed by three-level circuit with high conversion efficiency. |
DC/DC supports various types of energy storage batteries or photovoltaic modules, and can also realize DC remote supply voltage and power control. | Advanced interleaving control technology, ripple current is small, prolong battery life. |
DC/DC has two inputs, can be paralleled, can be independent, to achieve multi-channel MPPT, multi-channel battery optimization management. | Using harmonic suppression patented technology, intelligently adapt to industrial and commercial, micro-grid, distribution station terminal and other diverse scenarios. |
The micro-grid intelligent management system self-identifies the number and function of modules, integrates a variety of operating strategies and communication interfaces, unified scheduling, and intelligent management. |
Product Parameters:
Port | Mains supply | Load | PV | Energy storage | Charging pile | Remote feeding | ||||||||||||||
Rated power | 100kW | 100kW | 50kW | 50kW | 60kW | 50kW | ||||||||||||||
Rated voltage | 400Vac | 400Vac | 600Vdc | 600Vdc | 750Vdc | 800Vdc | ||||||||||||||
Rated current | 144A | 144A | 80A*2 | 80A*2 | 80A | 60A | ||||||||||||||
Power factor range | -1 lead ~+1lag | |||||||||||||||||||
Working model | constant power/ bus stabilization | constant voltage | MPPT | constant power/ bus stabilization | constant voltage | constant voltage | ||||||||||||||
Voltage range | 400Vac±15% | 200~725Vdc | 200~725Vdc | 600~750Vdc | 800~950Vdc | |||||||||||||||
Max current | 158A | 158A | 80A*2 | 80A*2 | 80A | 60A | ||||||||||||||
Input circuit | 1 | 1 | 2 (can be 2 independent or parallel to1road) | 1 | 1 | |||||||||||||||
Unbalanced load capacity | 100%3-phase independent contro | |||||||||||||||||||
Common params | ||||||||||||||||||||
Dimension | 900*950*2300 mm | |||||||||||||||||||
Weight | 300kg(transformer-free),830kg(Including power frequency transformer) | |||||||||||||||||||
Protection class | IP54 | |||||||||||||||||||
Operating temperature | -25~60℃(derating above 45°C) | |||||||||||||||||||
Cooling method | forced air cooling | |||||||||||||||||||
Noise | <70dB | |||||||||||||||||||
Altitude | 3000m(more than 3000m derating) | |||||||||||||||||||
Communication interface | RS485/CAN2.0/Ethernet /dry contact | |||||||||||||||||||
Configuration Recommendation | ||||||||||||||||||||
Uninterrupted power supply for critical loads | Configure STS module and the maintenance bypass switch | |||||||||||||||||||
Microgrid pluripotent powersupply | Configure power frequency transformer | |||||||||||||||||||
Distribution area benefit from each other | Configure power frequency transformer and save STS module | |||||||||||||||||||
Storage and charging station,dynamic capacity | Economize power frequency transformer;Save the STS module | |||||||||||||||||||
Combined light storage | Energy storage battery directly attached bus,save DC/DC module |